Limit 1: inrush
- At switch-on each driver draws a short, large pulse. Enough of them add up and trip the breaker, even though the running current is fine.
- The datasheet gives how many drivers a C 16 A takes. Other breakers use Helvar's conversion table: B10 37 %, B16 60 %, B20 75 %, C10 62 %, C16 100 %, C20 125 %.
- Rounded down.