Picking a Helvar sensor comes down to three questions: what shape is the space, how high is the ceiling, and is the controller DALI-2 multi-master or one of the older routers. Get those right and the rest is placement.
The DALI-2 sensors at a glance
Figures from Helvar's product data, at the nominal mounting height.
| Sensor | Senses | Coverage | Mounting height | Typical use |
|---|---|---|---|---|
| 320D2 | PIR | 8 m diameter, 116° | 2.5 m | Offices, meeting rooms, toilets |
| 321D2 | PIR and light | 8 m diameter, 116° | 2.5 m | Rooms with daylight |
| 3430D2 | PIR and light | 40 m, 166° | 2.5 m | Long corridors |
| 3440D2 | PIR and light | 24 m diameter, 156° | 2.5 m | Large open areas |
| 322D2 | PIR and light | 21 m diameter, 70° | 15 m | Warehouses, factories (IP65) |
| 324D2 | PIR and light | 7 m diameter, 109° | 2.5 m | Inside a luminaire, Zhaga R44 slot |
Each draws 10 mA from the DALI bus, which matters when you count bus current on a line with many sensors.

Presence, absence and daylight
A multisensor does two jobs. The PIR part detects movement, and the controller decides what to do with it: switch on when someone enters (presence), or only switch off when the room empties and leave switching on to the wall panel (absence). Absence is often the better choice in meeting rooms and private offices, where people do not want lights coming on every time they walk past the door.
The light sensor measures the light falling on the area below it, and the controller dims the fittings to hold a target level as daylight changes. That works best in the row of fittings nearest the window. Set the target on site with a meter, not from a drawing.
Match the sensor to the controller
The D2 sensors are DALI-2 control devices. Helvar lists them for use with its 945 and 950 multi-master controllers and the ActiveAhead range. The 905, 910 and 920 routers do not support DALI-2 control devices, so on those systems Helvar's non-D2 sensors, such as the 320, 321 and 322, are the ones to use.
This is easy to get wrong on a schedule. Check the controller before ordering sensors.
Outside and awkward spaces
- 329 External Light Sensor: IP65, wall mounted outdoors, so indoor levels can follow the daylight outside.
- 342 Acoustic Sensor: combines audio and infrasound detection, with a 50 m detection diameter. Helvar suggests it for corridors, stairwells and single-floor car parks where line-of-sight PIR struggles.
- 341 Corridor PIR: wall mounted, covering a 100° sector with a 41 m radius.

Placement tips from site
- PIR sees movement across its field better than towards it. Place sensors so people walk across the pattern.
- Keep sensors away from supply air diffusers and direct sun on the lens.
- In rooms where people sit still for long periods, use a longer time delay rather than more sensors.
See the full Helvar sensor range on our controls page, or send us a reflected ceiling plan and we will mark up sensor positions.