The Helvar 905, 910 and 920 are the same family of DIN rail application controllers, networked over Ethernet, and the choice comes down to how many DALI subnets you need and whether DMX or SDIM is involved. The 905 has one subnet, the 910 has two, and the 920 adds DMX and SDIM to the 910's two.
Side by side
All figures are from Helvar's datasheets.
| 905 | 910 | 920 | |
|---|---|---|---|
| DALI subnets | 1 | 2 | 2 |
| DALI devices | 64 | 128 (64 per subnet) | 128 (64 per subnet) |
| DALI output current | 240 mA guaranteed | 2 x 240 mA guaranteed | 2 x 240 mA guaranteed |
| DMX | No | No | In/out, 512 addresses |
| SDIM and override input | No | No | Yes |
| Power consumption | 13 VA | 23 VA | 23 VA |
| Size | 160 x 100 x 58 mm (9U DIN rail) | ||
| Network | 1 x RJ45, 10/100 Mb/s Ethernet | ||
What they have in common
Each router has a built-in real-time clock and DALI power supply, works out of the box for basic control, and is programmed in Helvar's Designer software for anything more. Helvar's description is that all data is stored in the routers themselves, with no central controller, so no single unit failing takes the whole system down. A PC is only needed for programming and diagnostics.
Routers network together over Ethernet into one system, so a large building is many routers working as one, each looking after its own subnets.

The DALI-2 point
All three are certified as DALI-2 single-master application controllers for control gear. That means DALI-2 drivers are fine. Helvar is explicit that DALI-2 control devices (third-party DALI-2 sensors and panels) are not supported on these routers. They use Helvar's DIGIDIM sensors and panels instead.
If a specification calls for DALI-2 sensors and panels on the bus, Helvar's answer is the newer multi-master controllers: the 945 with two DALI-2 subnets and the 950 with four.
Which one to pick
- 905: a single room or small area, or spread across a building where each area has its own small panel.
- 910: the workhorse for most floors. Two subnets per DIN rail slot keep panel boards compact.
- 920: when DMX fixtures, such as RGB facade or feature lighting, need to run in the same scenes as DALI, or when a fire alarm or similar override input is wanted directly on the router.
Most of our F&B and office projects mix them: 910s for the main load, a 920 where the bar or facade has DMX.

Next step
Send us the driver count per area and we will propose a router layout, or see the full Helvar range on our controls page.